Hi, I’m building a homelab watercooled unix server. I don’t want to buy expensive overpriced pre-mixes from ekwb or aquatuning. What cooling solution do datacenters use for water cooling?

What is the chemical solution? Does anyone know?

  • 51dusty@lemmy.world
    link
    fedilink
    English
    arrow-up
    10
    arrow-down
    1
    ·
    edit-2
    22 hours ago

    is liquid cooking cooling really necessary? critical data centers I have worked in use swamp coolers. cheaper, more efficient, more reliable, uses same water as your house…

    edit: d’oh! :)

    • nocturne@sopuli.xyz
      link
      fedilink
      English
      arrow-up
      6
      arrow-down
      1
      ·
      edit-2
      1 day ago

      Are you sure they use swamp coolers? Also known as evaporative coolers, they add moisture into dry air, making the air they are cooling very humid and only slightly cooler.

      • ramielrowe@lemmy.world
        link
        fedilink
        English
        arrow-up
        8
        arrow-down
        1
        ·
        1 day ago

        Practically all even semi-modern DCs are built for servers themselves to be air cooled. The air itself is cooled via a heat exchanger with a separate and isolated chiller and cooling tower. The isolated chiller is essentially the swamp cooler, but it’s isolated from the servers.

        There are cases where servers are directly liquid cooled, but it’s mostly just the recent Nvidia GPUs and niche things like high-frequency-trading and crypto ASICs.

        All this said… For the longest time I water cooled my home lab’s compute server because I thought it was necessary to reduce noise. But, with proper airflow and a good tower cooler, you can get basically just as quiet. All without the maintenance and risk of water, pumps, tubing, etc.

        • 51dusty@lemmy.world
          link
          fedilink
          English
          arrow-up
          2
          arrow-down
          1
          ·
          24 hours ago

          a chiller is not a swamp cooler.

          picture a fan with a wet sponge in front of it… that is a swamp cooler.

          • ramielrowe@lemmy.world
            link
            fedilink
            English
            arrow-up
            2
            arrow-down
            1
            ·
            edit-2
            18 hours ago

            Yea, it’s the combo of the chiller and cooling tower is analogous to a swamp cooler. The cooling tower provides the evaporative cooling. The difference is that rather than directly cooling the environment around the cooling tower, the chiller allows indirect cooling of the DC via heat exchange. And isolated chiller providing heat exchange is why humidity inside the DC isn’t impacted by the evaporative cooling. And sure, humidity is different between hot and cold isles. That is just a function of temperature and relative humidity. But, no moisture is exchanged into the DC to cool the DC.

            Edit: Turns out I’m a bit misinformed. Apparently in dry environments that can deal with the added moisture, DCs are built that indeed use simple direct evaporative cooling.

      • 51dusty@lemmy.world
        link
        fedilink
        English
        arrow-up
        4
        arrow-down
        1
        ·
        24 hours ago

        yes. I programmed and integrated swap coolers at Amazon data centers. when the cool air hits the hot aisles the humidity goes down.

        • nocturne@sopuli.xyz
          link
          fedilink
          English
          arrow-up
          1
          ·
          24 hours ago

          That is awesome! I had no idea swamp coolers could cool that well. The one in my shop can barely drop the temp 10-15 degrees below outside (on a good day). Sorry for doubting you, so used to people outside of arid climates not knowing what a swamp cooler is.

          • 51dusty@lemmy.world
            link
            fedilink
            English
            arrow-up
            4
            arrow-down
            1
            ·
            22 hours ago

            10-15 degrees is all you need to keep a “cold aisle” at 85degf, most places, on the worst day.

            IIRC Amazon figured out that individual components could actually run hotter within an acceptable replacement window.

            higher equipment replacement is more than offset by the fact they don’t have to do refrigerant based cooling which makes daily operation ridiculously cheap… no pumps or complicated mechanical devices to produce cooling… no people with special skills to maintain them, etc.

            • nocturne@sopuli.xyz
              link
              fedilink
              English
              arrow-up
              1
              ·
              edit-2
              21 hours ago

              That 10-15 (in my case) relies on no extra heat. When I have game nights it gets pretty toasty inside with 5 or so extra bodies in the shop.

              My last experience with a server room was in 2002 or 2003, and the rooms were kept in the mid to low 60s.

              • 51dusty@lemmy.world
                link
                fedilink
                English
                arrow-up
                2
                ·
                22 hours ago

                no doubt.

                I remember when you’d put a jacket on before you went in the halls… but now everyone wears shorts.

      • morbidcactus@lemmy.ca
        link
        fedilink
        English
        arrow-up
        4
        arrow-down
        1
        ·
        edit-2
        1 day ago

        Industrial cooling towers are usually evaporative in my experience, smaller ones are large fans moving air over a stack of slats that the return water is sprayed or piped over and the collects in well for recirculation, larger ones afaik (like what you’d see at power plants) operate the same idea. Top ups and water chemistry is all automated.

        Those systems have operation wide cooling loops that individual pieces of equipment tap into, some stuff uses it directly (see that with things like industrial furnaces) but smaller stuff or stuff that’s sensitive you’ll see heat exchangers and even then the server & PLC rooms were all air cooled, the air cons for them were all tied into the cooling water loops though.

        From a maintenance POV though, way easier to air cool, totally seen motor drive racks with failed cooling fans that have had really powerful external blowers rigged up to keep them going to the next maintenance window. Yeah, industrial POV but similar idea.

        • 51dusty@lemmy.world
          link
          fedilink
          English
          arrow-up
          2
          arrow-down
          1
          ·
          23 hours ago

          critical data centers use swamp coolers because they don’t have to treat the water or expose it to contamination from outside. they use straight domestic water… super cheap.

          if the conductivity gets too high, they dump the basin and fill with fresh… rinse and repeat.

    • over_clox@lemmy.world
      link
      fedilink
      English
      arrow-up
      6
      ·
      1 day ago

      liquid cooking?

      Haha, stupid sexy autocorrect, or honest typo, either way I got a good chuckle!